F
Model TC2900
Bus/String Multi-Drop Fiber
Optic Multiplexer

Features
- Support Bus/String Topology
- Async Data Rates up to 38.4 Kbps
- Separate Broadcast/Respond Channels
- Multimode & Single Mode (850/1300/1550nm)
- Distances up to 100Km
- 4, 8 or 12 Channels RS-232/422/485
- Tx & Rx LED's for Each Channel
- Anti-Streaming Capability
- Built-In Power Redundancy
- Local Dry Contact Alarm Relay
- Rackmount or Standalone
- Extend telephone lines with
TC1900 RS-232 or Fiber Phone Extenders
Description
Intended for Bus or String topologies, the
TC2900 Multi-Drop Fiber Optic Multiplexer links up to 12 monitoring devices (RTU's
or PLC's) fitted with RS-232, RS-422, or RS-485 (2 or 4 wire) interfaces to a
Host controller or CPU. It supports asynchronous data rates up to 38.4 Kbps.
The TC2900 works in a "polled-response" (also
called Slave/Master) types of communication network. Model TC2900 is the
Master, TC2901 is the Slave Units. A wide-range temperature version (-20°C to
70°C), Model TC2900T, is available for extreme environment applications.
Each TC2900 unit provides two pairs of fiber
interfaces and 4, 8 or 12 independent RS-232 and/or RS-422/485 channels. The
RS-232 channels can be used for data or as telephone extension with the Model
TC1900
"Quick-Talk" Telephone
Extenders. Diagnostic LED's include Tx and Rx for each channel, Power A,
Power B, VccA, VccB, SyncA, SyncB, LP-A and LP-B. An Anti-Streaming capability
is provided to prevent a single node failure (e.g. "babbling") from bringing
down the entire network.
Technical
Specifications
|
Data Rates |
|
Async
RS-232/422/485 |
Up to 38.4 Kbps |
|
Optical |
|
Transmitter |
ELED, ELED, LASER* |
|
Receiver |
PIN Diode |
|
Wavelength |
850nm, 1300nm Multimode
1300nm, 1550nm Single Mode |
|
Fiber Optic
Connectors |
ST or FC |
Loss Budget*
(850nm, 1300nm, 1550nm) |
Multimode (62.5/125µm): 15dB
Single Mode (9/125µm): 15dB |
|
Electrical
|
|
Connector |
RJ11 Female |
|
Interface |
RS-232 (DTE or DCE), RS-422, or
RS-485 (2 or 4 wire) |
|
System
|
|
Bit Error Rate |
1 in 109 or better |
|
Diagnostic
Functions |
|
Local & Remote Loopback, Signal
Generator, Master/Slave |
* Contact factory for higher requirements |
|
Alarm |
|
Dry Contact |
Normal OPEN |
|
Visual
Indicators |
|
System Status |
PWR A, PWR B, VccA, VccB |
|
Electrical
Signal Status |
Tx, Rx (for each channel) |
|
Optical Signal
Status |
TxA, RxA, TxB, RxB, SYNC A, SYNC
B, LPA, LPB |
|
Power
|
|
Standard |
12VDC @ 800mA |
|
Optional |
24VDC, -48VDC, or 115/230VAC
(with external power cube) |
|
Temperature
|
|
Operating |
-10° to 50°C |
|
Hi-Temp
(optional) |
-20° to 70°C |
|
Storage |
-40° to 90°C |
|
Humidity |
95% non-condensing |
|
Physical
(Standalone/Wallmount Unit) |
|
Height |
6.71 cm) 2.6" |
|
Width |
18.10 cm) 7.1" |
|
Depth |
24.89 cm) 9.8" |
|
Weight |
(1.82 kg) 4 lbs. |
|
Typical Application
(Application Questions)

|